Article for Facility Managers

What to Expect from a Commercial Kitchen Exhaust System Inspection

A commercial kitchen exhaust system inspection tells you whether your system holds grease that needs to be cleaned, section by section, from the hood to the rooftop fan. This article explains what a thorough inspection covers, how grease is measured, what you should receive afterward and how often the California Fire Code requires one.

It is written for facility managers, chief engineers and directors of facilities at hotels, hospitals, casinos, campuses and other properties with commercial kitchens. SDI Quality, family-owned for more than 35 years, inspects and cleans kitchen exhaust systems across Southern California.

Why the Inspection Comes First

NFPA 96 governs commercial kitchen exhaust systems. The current edition is 2024. It requires grease removed from the system to a fire-safe level.

In California, the 2022 California Fire Code, Section 606.3.3, turns that into a sequence. Table 606.3.3.1 sets how often the system must be inspected.

Section 606.3.3.2 says that when an inspection finds grease deposits, the system must be cleaned in accordance with ANSI/IKECA C10. Section 606.3.3.3 makes records and tags code requirements.

The inspection is the step that decides what happens next. A careful inspection gives you a clear answer either way: the system is in good order, or specific sections need cleaning.

How Often the California Fire Code Requires an Inspection

Table 606.3.3.1 sets inspection frequency by the type and volume of cooking. It is an inspection frequency, not a cleaning frequency. In California, this table, not the one in NFPA 96, sets the interval.

Inspection frequency per California Fire Code Table 606.3.3.1 (2022). This is an inspection frequency table, not a cleaning frequency table.
Cooking operationInspection frequency
Solid fuel cookingMonthly
High-volume operations: 24-hour cooking, charbroiling, wok cookingEvery 3 months
All other cooking operationsEvery 6 months
Low-volume operations: places of worship, seasonal businesses, senior centersEvery 12 months

A hotel, hospital or casino kitchen that cooks 24 hours a day or runs charbroilers or woks falls in the 3-month row. A property with several kitchens may have systems in different rows, so track each exhaust system and its interval separately.

What the Inspection Covers, From Hood to Roof Fan

A thorough inspection follows the whole path the exhaust air takes, not only the part of the hood you can see from the cook line.

The Hood

The inspection starts at the hood, where the exhaust path begins.

The Duct, Including the Horizontal Runs

The duct is opened at its access panels and inspected section by section, vertical and horizontal. The horizontal runs between the hood and the roof fan are the sections most often under-cleaned, because they can be reached only through access panels. A horizontal run that is never opened is never cleaned, however clean the hood looks.

The Rooftop Exhaust Fan

On the roof, the inspection covers the exhaust fan, the last section of the exhaust path.

Access to Every Section

The inspection also records any section of duct that cannot be reached because it has no access panel. Access panels at changes of direction are a California Mechanical Code item, not an upsell. A section that could not be reached is a finding in itself, and it belongs in the result.

How Grease Is Measured

The NFPA 96 fire-safe level is measured, not judged by eye. The technician checks grease depth with a depth gauge, also called a grease comb, at each section.

NFPA 96 does not require a duct to look new. Some residue that cannot sustain combustion is acceptable. What matters is whether the grease depth in each section is at the fire-safe level, and that is the question the depth gauge answers.

When the inspection finds grease deposits, Section 606.3.3.2 requires the system to be cleaned in accordance with ANSI/IKECA C10. Read more about our exhaust system inspection and kitchen exhaust cleaning services.

What You Should Receive Afterward

The result of an inspection should be specific enough that you could walk the system yourself and find each point. From SDI's zero-cost comprehensive system inspection, you receive:

  • Photos of what we find, section by section, including the horizontal duct runs reached through access panels.
  • A comprehensive NFPA 96 fire safety analysis of the hood, duct and fan.
  • Any section that could not be reached, and what it needs, such as a new access panel.

Section 606.3.3.3 makes records and tags code requirements: a record naming the individual and the company that did the work, and a service tag posted in a conspicuous location. SDI's NFPA 96 compliant work comes with photo documentation of every section.

The photos matter most for the sections no one on your team will see. Facility managers cannot climb into a duct, and photos of every section are how you know the hidden runs were inspected and cleaned.

How to Prepare Your Facility

A little preparation lets the inspection reach every section on the first visit:

  • Agree on a time with your kitchen or food service team, so the cook line is clear when the technician arrives.
  • Arrange roof access with your engineering team.
  • Note where the ceiling access panels are, especially above the horizontal duct runs.
  • Have the last record and the date on the current service tag ready, so the result can be compared with the previous service.

If you already have a provider, an inspection is a way to verify the system's condition. Either result is useful: confirmation that the system is in good order, or a list of the sections that need attention.

Who Performs SDI's Inspection

SDI Quality is IKECA certified, holding both CECS (Certified Exhaust Cleaning Specialist) and CESI (Certified Exhaust System Inspector), and its supervisors carry them.

  • More than 30 trained and certified technicians.
  • $10 million in insurance coverage.
  • Avendra Preferred Service Partner.
  • A+ BBB rating, and family-owned for more than 35 years.
  • NFPA 96 compliant work, with photo documentation of every section.

For the full set of NFPA 96 and California Fire Code requirements, see our NFPA 96 compliance guide, or read answers to common questions on our FAQ page.

Common Questions

What does a kitchen exhaust system inspection cover?

A thorough inspection covers the whole exhaust path: the hood, the duct opened at its access panels (including the horizontal runs), and the rooftop exhaust fan. It also records any section that cannot be reached because it has no access panel.

How often must a kitchen exhaust system be inspected in California?

California Fire Code Table 606.3.3.1 sets inspection frequency by the type and volume of cooking: solid fuel cooking monthly; high-volume operations (24-hour cooking, charbroiling, wok cooking) every 3 months; all other cooking every 6 months; low-volume operations (places of worship, seasonal businesses, senior centers) every 12 months.

How is grease measured during an inspection?

Grease depth is measured with a depth gauge, also called a grease comb. NFPA 96 requires grease removed to a fire-safe level, and some residue that cannot sustain combustion is acceptable.

What is the difference between an inspection and a cleaning?

An inspection finds out whether the system holds grease that needs to be cleaned. A cleaning removes it. Under California Fire Code Section 606.3.3.2, when an inspection finds grease deposits, the system must be cleaned in accordance with ANSI/IKECA C10.

Schedule a Zero-Cost Comprehensive System Inspection

Find out where your kitchen exhaust system stands. We inspect the hood, duct and fan, photograph what we find and share the photos with you.

Schedule a Zero-Cost Inspection

See where the facility's kitchen exhaust system stands against NFPA 96. Tell us about the facility and we'll call to set a time for a zero-cost inspection, or call 800-794-2345.

Zero-cost inspection, no obligation. Your information stays with SDI.